Refrigeration cycle / water system diagram, 1. water system diagram, Zone1 zone2 – Toshiba HWS-802XWHT6-E User Manual

Page 33

Advertising
background image

32

Toshiba

7

Refrigeration Cycle / Water System Diagram

7-1. Water System Diagram

M

M

Fan coil unit

Radiator unit

Floor

heating

By-pass valve

(locally procured)

By-pass valve

(locally procured)

Moterized mixing valve

(locally procured)

AC230V

Buffer tank(locally procured)

AC pump

(locally procured)

AC pump

max : 10bar

Strainer

(locally procured)

40 mesh

Motorized 3-way valve

(locally procured)

AC230V

Booster heater

(local)

2-way valve for

cooling mode

(locally procured)

AC230V

Safety valve

set : 3.5bar

Boiler

(local)

Drain cock for water charge

(locally procured)

Cylinder heater

Ø

1 : 2.75kW

Relief valve(UK)

90°C

10 bar

Water outlet

Water inlet

Reducing

valve(UK)

3.5bar

Pressure relief

Set value : 7bar(UK)

Water heat exchanger

max : 10bar

Backup heater

Ø

1 : 3kW

Ø

3 : 6kW

Ø

3 : 9kW

Flow sw

Thermal protector

(auto)

set : 75 ± 3°C

Thermal protector

Single operation

set : 95 ± 5°C

Low pressure sensor

Pressure switch

4.15MPa

Expansion vessel

set : 1bar

Pressure relief valve

set : 3bar

Menometer

gage : - 6bar

Water vent

valve

Air vent valve

Outdoor unit

8,11,14kw

Thermal cut-out

(manual reset)

82°C (+3k/

-2k)

zone1

zone2

TFI

TTW

TC

TWO

THO

TWI

Hot water cylinder

Local hot water system