[Suction temperature sensor (TS) failure]

[F13]

<Indication 1> <Indication 2>

[Heat sink temperature sensor (TH) failure]

[F15]

<Indication 1> <Indication 2>

[Heat exchanger sensor (TE, TS) wrong wiring]

[F31]

<Indication 1> <Indication 2>

[EEPROM failure]

Check code

Outdoor LED

indication

Check and Action procedure

(No specific description indicates outdoor unit parts.)

TS sensor connector
(CN600) is connected

Correct TS sensor
connection

Replace outdoor control board

No

Yes

TS sensor resistance
characteristic is normal

Replace TS sensor

No

Yes

Replace outdoor control board

TE and TS sensor is
attached to the correct position.

Correct sensor attaching
position

Replace outdoor control board

No

Yes

TE sensor resistance
characteristic is normal

Replace TE sensor

No

See the
characteristic table

on page 101

See the
characteristic table

on page 101

Yes

TS sensor resistance
characteristic is normal

Replace TS sensor

No

Yes

Check outdoor control board

If defective, replace it