[F07] Error TL sensor failure

[F08] Error TO sensor failure

[F10] Error TWI sensor failure

Correct TL sensor
connection

Replace TL sensor

No

No

TL sensor

connector (CN604) is

connected

Yes

TL sensor

resistance characteristic

is normal

Yes

Start

Replace water heat exchange control board

(See characteristic table on page 101)

Correct TO sensor
connection

Replace TO sensor

No

No

TO sensor

connector (CN602) is

connected

Yes

TO sensor

resistance characteristic

is normal

Yes

Start

(See characteristic table on page 101)

Replace water heat exchange control board

Correct TWI sensor
connection

Replace TWI sensor

No

No

(See characteristic table on page 101)

TWI sensor

connector (CN205) is

connected

Yes

TWI sensor

characteristic is normal

Yes

Start

Replace water heat exchange control board