Toshiba HWS-802XWHT6-E User Manual

Page 95

Advertising
background image

94

Toshiba

[P03]

<Indication 1> <Indication 2>

[Abnormal outlet temperature]

[P04]

* Any of the following abnormality may occur.

Seeing the LED on the outside board can determine which abnormality occurs.

Power source failure (Vdc), Hi pressure protection operation, Case thermostat operation

<Indication 1> <Indication 2>

[Case thermostat operation]

→ See [H04] details

<Indication 1> <Indication 2>

[Power source failure (Vdc)]

→ See [P05] details

<Indication 1> <Indication 2>

[Hi pressure protection operation]

→ See [P20] details

[P05]

<Indication 1> <Indication 2>

[Power source failure (voltage defective, open phase)]

Check code

Outdoor LED

indication

Check and Action procedure

(No specific description indicates outdoor unit parts.)

No gas leakage.
Appropriate refrigerant amount.

Correct defective portion
Re-charge refrigerant

Check outdoor control board

If defective, replace it

No

Yes

Pulse motor valve is normal.

Correct defective portion
Replace defective parts

No

Yes

Abnormally over loaded

Deal with or remove
causes

Yes

No

CN603 connector is normal.
TD sensor resistance is normal

Correct connector
Replace sensor

No

Yes

Check outdoor control board

If defective, replace it

Power voltage abnormally
drops or rise (230ACV ± 23V)

Check electric work

Yes

No