[H02]

<Indication 1> <Indication 2>

[Compressor lock]

[H04]

<Indication 1> <Indication 2>

[Case thermostat operation]

[L10]

<Indication 1> <Indication 2>

[Model not set] Only when service board is used

Check code

Outdoor LED

indication

Check and Action procedure

(No specific description indicates outdoor unit parts.)

Power voltage is normal.
230ACV ± 23V

Improve power line

Check outdoor board

If defective, replace it

No

Yes

Compressor is normal.

Lock compressor and
replace it.

No

Yes

Refrigerant stays inside.

No

Yes

TE, TS sensor pulse
motor valve check
If defective, replace

Pulse motor valve operates
normally.

No

Yes

Wiring connection is normal.
Compressor lead (board side,
compressor side) reactor, power lead

Check and correct
wiring connection

No

Yes

CN609 connector and case
thermostat is normal.

Correct connector
Replace case thermostat

Check for piping collapse and break.

If defective, repair or replace it.

No

Yes

If case thermostat is short circuited,
cooling and heating can operate.

Check outdoor board
If defective, replace it

No

Yes

No gas leakage.
Enough Refrigerant.

Correct defective portion
Re-charge refrigerant

No

Yes

Service valve is fully opened.

Open fully service valve

No

Yes

Pulse motor valve is normal.

Correct defective portion
Replace defective parts

No

Yes

Cut jumper line by following the instruction
comes with the service board package

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 92 Monday, October 5, 2009 2:09 PM