Defect mode detected by the outdoor unit – Toshiba HWS-802XWHT6-E User Manual

Page 71

Advertising
background image

70

Toshiba

Defect mode detected by the outdoor unit

O ... Possible
× .... Not possible

Check

code

Diagnostic functional operation

Determination and action

Number of

abnormalities

for

confirmation

Detailed

item

Operational cause

Backup
present

Automat

ic reset

F04

TD sensor error

Open or short circuit in the discharge

temperature sensor.

O

×

1. Check the resistance value and

connection of the discharge sensor
(TD).

1

85

99

F06

TE sensor error

Open or short circuit in the heat

exchange temperature sensor.

O

×

1. Check the resistance value and

connection of the heat exchange
temperature sensor (TE).

1

85

99

F07

TL sensor error

Open or short circuit in the heat

exchange temperature sensor.

O

×

1. Check the resistance value and

connection of the heat exchange
temperature sensor (TL).

1

86

99

F08

TO sensor error

Open or short circuit in the outdoor

temperature sensor.

O

×

1. Check the resistance value and

connection of the outdoor
temperature sensor (TO).

1

86

99

F12

TS sensor error

Open or short circuit in the suction

temperature sensor.

O

×

1. Check the resistance value and

connection of the suction
temperature sensor (TS).

1

100

F13

TH sensor error

Open or short circuit in the heat-sink

temperature sensor.

O

×

1. Check the resistance value and

connection of the heat-sink
temperature sensor (TH).

1

100

F15

TE, TS sensors error

Open or short circuit in the temperature

sensors.

O

×

1. Check for any wrong installation of

the heat exchange temperature
sensor (TE) and the suction
temperature sensor (TS).

1

100

F31

EEPROM error

O

×

1

100

H01

Compressor breakdown

1 When the operation frequency lowers

due to the current release 40 sec or
later after the compressor activation
and it stops by underrunning the
minimum frequency.

2 When the operation frequency lowers

due to the current limit control and it
stops by underrunning the minimum
frequency.

3 When an excess current is detected

0.8 sec or later after the compressor
activation.

O

×

1. Check the power supply voltage

(AC230 V±23 V).

2. Over-loaded condition of the

refrigeration cycle.

3. Check that the service valve is fully

open.

8

91

H02

Compressor lock

1 When the input current is more than

zero 20 sec or later after the
compressor activation and the
activation has not been completed.

O

×

1. Defect of compressor (lock)

– Replace the compressor.

2. Defect of compressor wiring (open

phase).

8

92

H03

Defect in the current detection circuit

O

×

1. Replace the outdoor inverter control

board.

8

92