[A09] Error Overheat prevention thermostat failure (Hot water supply/Heating operation)

Put water into water circuit
(Recommended: 1 - 2 Bar)

Replace heater unit
exchanger air vent valve

Replace flow switch

No

No

Water cycle contains water

Yes

Flow switch is normal

Yes

No

At normal temperature,

overheat preventive thermostat

is normal

Yes

Start

Replace water heat exchange control board

or overheat preventive thermostat failure

*Replace water heat exchange control board or overheat preventive thermostat failure: After the control
board is replaced, if the same operation repeats, the overheat preventive thermostat is determined as
defective (does not operate at 75°C).