9-6-2. Outdoor unit

No.

Component name

Check procedure

1

Compressor

Type

DA220A2F-22L

(802H-E)

DA422A3F-25M

(1102,1402H-E)

Measure the resistance value of each winding with a tester.

2

Outdoor fan motor

Type

ICF-280-A60-1

(802H-E)

ICF-280-A100-1

(1102,1402H-E)

Measure the resistance value of each winding with a tester.

3

4-way valve coil

Type

VHV-01AP552B1

Measure the resistance value.

1473

Ω ± 103 Ω

4

Pulse motor valve coil

Type

CAM-MD12TF-15

(802H-E)

Measure the resistance value.

Type

UKV-A038

(1102,1402H-E)

5

Suction temperature (TS) sensor

Heat exchange temperature

(TE) sensor

Outdoor temperature (TO)

sensor

Remove the connector and measure the resistance value with a tester.

10-20 k

Ω (Normal temperature)

6

Discharge temperature (TD)

sensor

Remove the connector and measure the resistance value with a tester.

Red

White

Black

Location

Resistance

value

Red

White

1.04-1.16

Ω

White

Black

1.04-1.16

Ω

Black

Red

1.04-1.16

Ω At 20°C

Red

White

Black

Location

Resistance value

802H-E

Red

White

32.6 ± 3.3

Ω

White

Black

Black

Red

1102,1402H-E

Red

White

14.8 ± 1.5

Ω

White

Black

Black

Red

1 White

6 Red

3 Orange

Yellow

2

Blue

4

M

Location

Resistance

value

Red

White, Orange

42-50

Ω

Red

Yellow, Blue

42-50

Ω

Condition 20°C

M

1 Black

6 Gray

3 Red

Yellow

2

Grey

6

Orange

4

Location

Resistance

value

Grey

Black, Red

43-49

Ω

Grey

Yellow, Orange

43-49

Ω

Condition 20°C

Temperature

0°C

10°C

20°C

30°C

Sensor (k

Ω)

Outdoor heat exchange temperature sensor (TE)

33.8

20.4

12.6

8.0

Suction temperature sensor (TS)

Temperature

0°C

10°C

20°C

30°C

Sensor (k

Ω)

Discharge temperature sensor (TD)

161.3

99.0

62.4

40.2