[A02] Error Temperature rise and error short circuit

Replace TWI, TWO,
and THO sensors

No

(TWI,TWO,THO 70°C)

TWI, TWO, and THO

sensor characteristics are

correct

Yes

No

Water outlet

temperature is 70°C

or higher

Yes

Correct water circuit
(To prevent hot water of
other circuits from entering)

Yes

Hot water from

boiler or other circuits does

not come in

No

Failure of backup heater
(Too large heater input,
thermostat short circuit)

Replace heater unit

Yes

Backup heater is energized

No

(Measure heater current)

Start

Replace water heat exchange control board

Yes

Flow switch is normal

No

Replace flow switch

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 75 Monday, October 5, 2009 2:09 PM