Toshiba HWS-802XWHT6-E User Manual

Page 149

Advertising
background image

148

Toshiba

4

Electric parts
replacement

1. Control board

1) Perform the step 1-1.

WARNING

For 1 minute after the power is turned off, do not
disassemble the inverter to prevent an electric
shock.

2) Remove the connector connected to the control

(Hydro power source, temperature sensor, electric
control valve coil, 4-way valve coil, compressor
case thermostat, fan motor)

* Remove the connector by releasing the lock in the

housing.

3) Remove the lead cable connected to the control

board.
Compressor lead U: CN200 Red

V: CN201 White
W: CN202 Black

Reactor lead CN05 White

CN06 White Relay connector

4) Remove the ground wire of the control board.

(Truss B tight screw Ш4 Ч 6, 1 screw)

5) Remove the fixed screws of the control board.

(Collar screw for fixing element Ш3 Ч 16, 9 screws,
Pan S-tight screw for fixing the board Ш3 Ч 20, 1
screw)

6) Remove the control board.

(Supporter 5 positions)
Note) Removing the control board may be difficult

due to the heat release grease for the heat
sink.

7) Attach a new control board.

Note) • Be careful for not taking the compressor

lead V: CN201 White for the reactor lead
CN05 or 06 White.
(The compressor lead has a transparent
sleeve at its ring terminal. The reactor
lead ring terminal does not have sleeve.)

• Be sure to attach the insulating sheet.

(Applying beforehand a bit of heat
release grease to the back side of the
insulating sheet can easily paste the
sheet to the heat sink.)

No.

Exchange parts

name

Work procedure

Remarks

Control board

Control board

Insulating
sheet

Hear release
grease

Fan motor (upper)

Fan motor (lower)

Reactor lead

Compressor lead

4-way valve coil

Temperature
sensor

Indoor power source

Motorized control coil

Screw for fixing
board

Screw for fixing element
(9 positions)

Ground wire

Compressor
case
thermostat

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 148 Monday, October 5, 2009 2:09 PM