Toshiba

[A11] Error Release protection operation

Replace flow switch

Remove waste

Flow switch is normal

Secure water
circulation amount

Circulation flow
shortage

Waste stuck inside
water circuit

12 M or longer water
pipe to a branch,
or 5 or less branches

Remove sufficiently
excess air

Place buffer tank and
the second pump

No

Excess air

noise comes from

inside pump

Chattering

noise comes from

flow switch

Start

No

No

Yes

Attach TWI sensor

No

TWI sensor is

attached to pipe

Yes

Replace TWI or TWO sensor

No

TWI and TWO

sensor characteristics

are normal

Yes

Yes

Yes

Replace water heat

exchange control board