*1 Heating performance measurement conditions: outside air temperature 7 or 6 °C, water supply temperature 30 °C, outlet temperature 35 °C, refrigerant piping length 7.5 m (no height

difference), capacity 97%, COP 95%, operating noise +3 dB

*2 Cooling performance measurement conditions: outside air temperature 35 °C, water supply temperature 12 °C, outlet temperature 7 °C, refrigerant piping length 7.5 m (no height

difference), capacity 97%, COP 95%, operating noise +3 dB

*3 • The remote controller should be shipped with the hydro unit.

• Use two 1.5-meter wires to connect the hydro unit with the remote controller.

*4 The outdoor unit operating noise is measured at the point of 1m away from the unit back surface center and 1m high from the ground. The hydro unit operating noise is measured at the

point of 1m away from the unit front surface center.
The value of the operating noise varies depending on room structure where the unit is installed.

*5 Do not leave the hydro unit at 5 °C or below.
*6 Check the water piping for leakage under the maximum operating pressure.

Unit name

Hydro unit

HWS-802XWHM3-E, 802XWHT6-E

Outdoor unit

HWS-802H-E

Heating capacity *1 (kW)

8.0

Cooling capacity *2 (kW)

6.0

Variable range of compressor frequency

10 - 70 Hz

Power source

Single phase 50Hz 230V

Operation mode

Heating

Cooling

Electric characteristic *1 *2

Hydro unit

Current (A)

0.98

0.46

Power (kW)

0.101

0.097

Power factor (%)

91.5

91.7

Outdoor unit

Current (A)

8.26

8.90

Power (kW)

1.859

2.033

Power factor (%)

97.8

99.3

Total

Starting current (A)

9.24

9.36

Operating noise *1 *2 *4

Hydro unit (dB(A))

29

29

Outdoor unit (dB(A))

49

49

Coefficient of performance *1 *2

4.08

2.82

Hydro unit

Outer dimension

Height (mm)

925

Width (mm)

525

Depth (mm)

355

Net weight (kg)

50

Color

Silky shade (Munsell 1Y8.5/0.5)

Remote controller
Outer dimension *3

Height (mm)

120

Width (mm)

120

Depth (mm)

20

Circulating pump

Motor output (W)

125 (MAX)

Flow rate (L/min)

22.9

17.2

Type

Non-self-suction centrifugal pump

Heat exchanger

Plate-type heat exchange

Outdoor unit

Outer dimension

Height (mm)

890

Width (mm)

900

Depth (mm)

320

Net weight (kg)

63

Color

Silky shade (Munsell 1Y8.5/0.5)

Compressor

Motor output (W)

1400

Type

Twin rotary type with DC-inverter variable speed control

Model

DA220A2F-22L

Fan motor

Standard air capacity (m

3

/min)

50.0

Motor output (W)

60

Refrigerant piping

Connection method

Flare connection

Hydro unit

Liquid

Ø9.52

Gas

Ø15.9

Outdoor unit

Liquid

Ø9.52

Gas

Ø15.9

Maximum length (m)

30

Maximum chargeless length (m)

30

Maximum height difference (m)

±30

Minimum length (m)

5

Refrigerant

Refrigerant name

R410A

Charge amount (kg)

1.8

Water piping

Pipe diameter

R1 1/4

Maximum length (m)

None (Need the flow rate 17.5 /min or more)

Maximum height difference (m)

±7

Maximum working water pressure (kPa)

300

Operating temperature range

Hydro unit (°C)

5-32

Outdoor unit (°C)

-20-43

Operating humidity range

Hydro unit (%)

15-85

Outdoor unit (%)

15-100

Wiring connection

Power wiring

3 wires: including ground line (Outdoor unit)

Connecting line

4 wires: including ground line