16-3. Service support functions (LED indication, Switch operation method)
The following settings are available with dip switches.

(1) Overview

Using 3 dip switches (SW802, SW803, SW804) and 2 push-button switches (SW800, SW801) can make settings
available and confirm operations.

For operation

For display

Note: All the LEDs have no color when off.

Part number

Specification

Operation details

SW800

Press button switch

This switch switches the indications of LED (D800 to D804) on the outdoor control board.

SW803

Dip switch

SW801

Press button switch

This switch enables users to perform a special operation for maintenance and inspection.

SW804

Dip switch

SW802

Dip switch

This switch performs initial settings. (See 8-4-6)

Part number

Specification

Operation details

D502

Amber LED

Signal display (signals from the hydro unit) of communication between hydro unit and
outdoor unit (serial communication)

D503

Green LED

Signal display (signals from the outdoor unit) of communication between hydro unit and
outdoor unit (serial communication)

D800 to D804

Yellow LED

Abnormality indication
All OFF of SW803 or the lit status of any of D800 to D804 indicates that the outdoor
control unit detects an abnormality.
Setting SW803 to other than OFF shows details with LED indication.

D805

Green LED

Energization indication
This LED lights when the outdoor unit is energized.
During a special operation with the SW801 or SW804 operation, this LED blinks.

1234

ON

1234

ON

1234

ON

D800
D801
D802
D803
D804
D805

SW804
SW801

SW800
SW803

LED indication switching switch

D503 (

Green LED

) ---

Serial signal (Outdoor to hydro)

D502 (

Amber

LED) ---

Serial signal (Hydro to Outdoor)

SW802 ---

Initial settings switching

D800

(Yellow LED)

D801 (

Yellow LED

)

D802 (

Yellow LED

)

D803 (

Yellow LED

)

D804 (

Yellow LED

)

D805 (

Green LED

) ---

Energization indication

Special operation switch (Operations
for maintenance and inspection)

Abnormality indication
and other indications

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 121 Monday, October 5, 2009 2:09 PM