[P20]

<Indication 1> <Indication 2>

[Hi pressure protection operation]

Check code

Outdoor LED

indication

Check and Action procedure

(No specific description indicates outdoor unit parts.)

No

Yes

Service valve is fully opened.

No

Open fully service valve

Yes

Outdoor TL sensor is normal.
(Measure resistance)

Cooling season
Cooling operation

Heating season
Heating operation

No

Replace sensor

Yes

Remove the disturbing
element

Yes

Outdoor fan is free from crack
or looseness.

No

Check outdoor fan
If defective, replace or tighten it

Yes

Outdoor fan operates normally.

No

Check the same item as
those for [P22] abnormality

Reset the power source and perform
a trail operation according to the season.

Something prevents outdoor unit
heat exchange
- Clogged heat exchanger
- short circuit

No

Yes

Check for refrigerant overcharged, clogged
cycle, pipe break, abnormal overload, etc.
If defective, repair defective portion

Check for refrigerant overcharged, clogged
cycle, pipe break, abnormal overload, etc.
If defective, repair defective portion

Remove the
disturbing element

Something prevents heat
exchange of hydro unit.
- Clogged filter
- Clogged heat exchanger
- Short circuit