Toshiba

[E04] Error

Outdoor unit operates

Group address

of remote controller is

correctly set

Yes

Check water heat exchanger

control board

If defective, replace it

Check outdoor control board

If defective, replace it

No

Check item code "14"

No

Yes

Hydro unit

Internal wiring and

connecting wire (1, 2, 3)

are correct

Correct wiring and
connecting wire

No

Yes

CN04 connector

and terminal block (1, 2, 3) wiring

are normal

Correct connector and
terminal block wiring

No

Yes

When power is

on again, D502 (Amber LED)

blinks

Check water heat
exchanger board
If defective, replace it

No

Yes

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 84 Monday, October 5, 2009 2:09 PM