Defect mode detected by the remote control – Toshiba HWS-802XWHT6-E User Manual

Page 74

Advertising
background image

73

Toshiba

Defect mode detected by the remote control

Check code

Diagnostic functional operation

Determination and action

Operational cause

Status of air-

conditioning

Condition

Not

displaying at

all

(cannot

operate by
the remote

control)

No communication between hydro
unit an remote controller
• The remote control wiring is not

connected correctly.

• The hydro unit has not been turned

on.

Stop

Defect in the remote control power
supply

1. Check the remote controller wiring.

2. Check the remote controller.

3. Check the hydro unit power supply

wiring.

4. Check the water heat exchange

control board.

E01

No communication between hydro
unit and remote controller
• Disconnection of the crossover

between the remote control and the
base unit of the indoor unit
(detected on the remote control
side).

Stop
(Automatic reset)

Displayed when
the abnormality
is detected.

Defect in the reception of the remote
control

1. Check the remote control crossover.

2. Check the remote control.

3. Check the hydro power supply wiring.

4. Check the water heat exchanger

board.

E02

Defect in the signal transmission
to the hydro unit.
(Detected on the remote control side)

Stop
(Automatic reset)

Displayed when
the abnormality
is detected.

Defect in the transmission of the remote
control

1. Check the transmitter circuit inside the

remote control.

… Replace the remote control.

E09

Several remote control base units
(Detected on the remote control side)

Stop
(The handset
continues)

Displayed when
the abnormality
is detected.

1.2 Check several base units with the

remote control

… The base unit is only one, and others

are handsets.