Toshiba HWS-802XWHT6-E User Manual

Page 139

Advertising
background image

138

Toshiba

4

Electric parts
replacement

1. Control board

1) Perform the step 1-1.

WARNING

For 1 minute after the power is turned off, do not
disassemble the inverter to prevent an electric
shock.

2) Remove the connector connected to the control

board.
(Hydro power source, temperature sensor, electric
control valve coil, 4-way valve coil, compressor
case thermostat, fan motor)

* Remove the connector by releasing the lock in the

housing.

3) Remove the lead cable connected to the control

board. (Torque at tightening is 1.47 ±0.1N•m)
Compressor lead U: CN200 Red

V: CN201 White
W: CN202 Black

Remove the power source cable from the power
source terminal block.
(Torque at tightening is 2.5 ±0.1N•m)

4) Remove the ground wire of the control board.

(Truss B tight screw Ш4 Ч 6, 1 screw)

5) Remove the fixed screws of the control board.

(Collar screw for fixing element Ш3 Ч 16, 7 screws,
Pan S-tight screw for fixing the board Ш3 Ч 20, 1
screw)

6) Remove the control board.

(Supporter 5 positions)
Note) Removing the control board may be difficult

due to the heat release grease for the heat
sink.

7) Attach a new control board.

Note) • Be careful for not taking the compressor

lead V: CN201 White for the reactor lead
CN05 or 06 White.
(The compressor lead has a transparent
sleeve at its ring terminal. The reactor
lead ring terminal does not have sleeve.)

• Be sure to attach the aluminium board

(Q201) and the insulating sheet (Q300).
(Applying beforehand a bit of heat
release grease to the back side of the
insulating sheet can easily paste the
sheet to the heat sink.)

No.

Exchange parts

name

Work procedure

Remarks

Control board

Control board

Aluminum board (Q201)

Insulating sheet (Q300)

Heat release grease

Fan motor

Reactor lead

4-way valve coil

Temperature
sensor

Indoor power source

Electric control valve coil

Screw for fixing board

Power source terminal block

Screw for fixing element (7 screws)

Ground wire

Compressor
case
thermostat

Compressor
lead

Reactor
lead

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 138 Monday, October 5, 2009 2:09 PM