Toshiba HWS-802XWHT6-E User Manual

Page 49

Advertising
background image

48

Toshiba

8-3.

Hydro Unit
Control

1) Capacity control (compressor, high-temperature release, low-temperature release)

This unit controls the compressor frequency and heater output so that the water outlet temperature matches the remote
controller set temperature.

1-1) Compressor control

• Calculates the different between the remote controller set temperature (TSC_H, TSC_F) and the water outlet

temperature (Hot water supply: THO, Heating: TWO).

• Sets the Hz signal correction amount that determines the number of compressor rotations by the temperature

difference.

• Detects the number of compressor rotations.
• Compares the Hz signal correction amount and the current operation Hz, and changes the compressor output

according to the difference.

* The control details are the same for hot water supply, heating, and cooling.

Item

Operation flow and applicable data, etc.

Temperature settings

(TSC_H, TSC_F)

Hz signal correction

Number of compressor

rotation detection

Remote controller

Water outlet temperature

(THO, TWO)

Hydro unit

TSC_H-THO for hot water supply

TSC_F-TWO

for heating/cooling

Inverter output change

Hz signal correction Operation Hz

Number of compressor

rotation change

Compressor frequency changeable range 10 Hz to 70 Hz (802, 1402H-E)

10 Hz to 60 Hz (1102H-E)

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 48 Monday, October 5, 2009 2:09 PM