14. Display Function of Set Temperature and Other Settings

Sensor temperature display calling

<Details>
This function calls the service monitor mode from the remote controller
to show the data of the remote controller, the hydro unit, and outdoor
unit.

<Procedure>

1

Press the TEST

and CL

buttons at the same time

for 4 seconds or longer to call the service monitor mode.

The service monitor lights up, and the temperature of CODE No.
"00" displays at first.

(See display

)

2

Press the TEMP.

button for temperature setting

to change the item code to one to be monitored.

The following table shows the item codes.

3

Pressing the TEST

button returns to the usual display.

Hydr

o unit data

Item code

Data name

Unit

00

Control temperature (Hot water cylinder)

°C

01

Control temperature (Zone1)

°C

02

Control temperature (Zone2)

°C

03

Remote controller sensor temperature

°C

04

Condensed temperature (TC)

°C

06

Water inlet temperature (TWI)

°C

07

Water outlet temperature (TWO)

°C

08

Water heater outlet temperature (THO)

°C

09

Floor inlet temperature (TFI)

°C

0A

Hot water cylinder temperature (TTW)

°C

0B

Mixing valve position

step

OE

Lo pressure (Ps) × 100

MPa

O

u

tdoor

uni

t

data

Item code

Data name

Unit

60

Heat exchange temperature (TE)

°C

61

Outside air temperature (TO)

°C

62

Discharge temperature (TD)

°C

63

Suction temperature (TS)

°C

65

Heat sink temperature (THS)

°C

6A

Current

A

6D

Heat exchanger coil temperature (TL)

°C

70

Compressor operation Hz

Hz

72

Number of revolutions of outdoor fan (lower)

rpm

73

Number of revolutions of outdoor fan (upper)

rpm

74

Outdoor PMV position × 1/10

pls

S

e

rv

ic

e d

a

ta

Item code

Data name

Unit

F0

Micro computer energized accumulation time

× 100h

F1

Hot water compressor ON accumulation time

× 100h

F2

Cooling compressor ON accumulation time

× 100h

F3

Heating compressor ON accumulation time

× 100h

F4

Built-in AC pump operation accumulation time

× 100h

F5

Hot water cylinder heater operation accumulation time

× 100h

F6

Backup heater operation accumulation time

× 100h

F7

Booster heater operation accumulation time

× 100h

1 3

2

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 118 Monday, October 5, 2009 2:09 PM