12

Toshiba

NOTE

• Make sure that the setting is appropriate so that liquid can be charged.
• A cylinder with siphon enables liquid to be charged without the cylinder turned upside down.

NOTE

• Because R410A is HFC mixed refrigerant, charging with gas changes the charged refrigerant composition,

causing the equipment characteristics to change.

[Cylinder with siphon]

[Cylinder without siphon]

Gauge manifold

Outdoor unit

Refrigerant
cylinder

Electronic balance

Gauge manifold

Outdoor unit

Refrigerant
cylinder

Electronic balance

Siphon pipe

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 12 Monday, October 5, 2009 2:09 PM