High pressure protection operation

When an abnormal stop occurs due to

the high pressure release control.

When the heat exchange temperature

sensor (TL) detects 63°C during the

cooling operation.

When the water outlet sensor (TWO)

detects 60°C during the heating or hot

water supply operation.

O

×

1. Check that the service valve is fully

open.

2. Defect of the pulse motor valve.

3. Check the outdoor fan system

(including clogging).

4. Over-filling of refrigerant.

5. Check the resistance value of the

heat exchange temperature sensor
(TL) and the water outlet
temperature sensor (TWO).

10

97

P22

Outdoor fan system error

When a DC fan rotor position detection

NG, element short circuit, loss of

synchronization, or abnormal motor

current occurs.

O

×

1. Check the lock status of the motor

fan.

2. Check the connection of the fan

motor cable connector.

3. Check the power supply voltage

(AC230 V±23 V).

1-4

98

P26

Short circuit of the compressor driver

element error

When an abnormal short circuit of IGBT

is detected.

O

×

1. P26 abnormality occurs when

operating with the compressor
wiring disconnected … Check the
control board.

2. No abnormality occurs when

operating with the compressor
wiring disconnected … Compressor
rare short.

8

98

P29

Compressor rotor position error

The rotor position in the compressor

cannot be detected.

O

×

1. Even if the connection lead wire of

the compressor is disconnected, it
stops due to an abnormality in the
position detection … Replace the
inverter control board.

2. Check the wire wound resistor of the

compressor. Short circuit
… Replace the compressor.

8

98

Check

code

Diagnostic functional operation

Determination and action

Number of

abnormalities

for

confirmation

Detailed

item

Operational cause

Backup
present

Automat

ic reset