[F20] Error TFI detach failure

[F23] Error Lo pressure sensor detach failure

Attach TFI sensor
to pipe

Replace TFI sensor

No

No

TFI sensor

is attached to pipe

Yes

TFI sensor

characteristic is normal

Yes

Replace TWI sensor

No

(See characteristic table on page 101)

(See characteristic table on page 101)

TWI sensor

characteristic is normal

Yes

Replace TWO sensor

No

(See characteristic table on page 101)

TWO sensor

characteristic is normal

Yes

Start

Replace water heat exchange control board

Attach lo pressure sensor

Replace lo pressure sensor

Yes

No

Lo pressure sensor

is detached (CN207, 212)

No

When operation

is stopped, lo pressure sensor

is normal *1

Yes

Start

*1 How to determine: When operation is stopped

Replace water heat exchange control board