Toshiba HWS-802XWHT6-E User Manual

Page 136

Advertising
background image

135

Toshiba

17

Water heat
exchanger assembly

1. How to remove

1) Perform the step 1-1, step 5, 6, and 8.
2) Remove the water pipe fixing board.

(ST2T Ш4 Ч 8, 2 screws)

3) Remove the refrigerant piping fixing board.

(ST2T Ш4 Ч 8, 3 screws)

4) Remove the nut of the heater connection.
5) Remove the fixed screws of the electric parts box

fixing board.
(ST2T Ш4 Ч 8, 4 screws)

6) Remove the side reinforcing board (left).

(ST2T Ш4 Ч 8, 6 screws) 3 for inside, 3 for outside

7) Remove the water heat exchanger fixing band.

(ST2T Ш4 Ч 8, 6 screws)

8) Remove the water heat exchanger assembly.

2. How to attach

1) Attach a new water heat exchanger assembly in the

reverse order of the removal.

2) Restore all piping and wiring as in the original state,

and check that there is no water or refrigerant
leakage.

No.

Exchange parts name

Work procedure

Remarks

• Close the water piping source valve and the valve

of water pipe connected to the hydro unit, and
then remove the refrigerant and water piping.

• Perform refrigerant recovery with the outdoor

unit.

• Disconnect all the power source cable, outdoor

unit connection cable, and cylinder connection
cable.

The heater connection uses a packing for water
seal. Be careful not to scratch the packing;
otherwise, water leakage may occur.

• After the water heat exchanger assembly

replacement repair, open the water supply source
valve and water piping source valve to pass
water through the hydro unit, and check that the
connection has no water leakage.

• After connecting the refrigerant pipe, check that

the connection has no refrigerant leakage.

Water
piping fixing

Refrigerant piping
fixing board

Nut

Electric parts
box fixing

Side reinforcing board (left)

Water heat exchanger assembly

Water heat exchanger
fixing band

The piping
structure slightly
differs in 14kW and
8kW specifications.

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 135 Monday, October 5, 2009 2:09 PM