F03] error tc sensor failure – Toshiba HWS-802XWHT6-E User Manual

Page 86

Advertising
background image

85

Toshiba

[F03] Error TC sensor failure

[F04] Error TD sensor failure

[F06] Error TE sensor failure

Correct TC sensor
connection

Replace TC sensor

No

No

TC sensor

connector (CN203) is

connected

Yes

TC sensor

resistance characteristic

is normal

Yes

Start

Replace water heat exchange control board

Correct TD sensor
connection

Replace TD sensor

No

No

TD sensor

connector (CN603) is

connected

Yes

TD sensor

resistance characteristic

is normal

Yes

Start

Replace water heat exchange control board

Correct TE sensor
connection

Replace TE sensor

No

No

TE sensor

connector (CN601) is

connected

Yes

TE sensor

resistance characteristic

is normal

Yes

Start

Replace water heat exchange control board

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 85 Monday, October 5, 2009 2:09 PM