Toshiba HWS-802XWHT6-E User Manual

Page 96

Advertising
background image

95

Toshiba

[P07]

<Indication 1> <Indication 2>

[Heat sink overheat failure]

[P15]

<Indication 1> <Indication 2>

[Gas leakage detection]

Check code

Outdoor LED

indication

Check and Action procedure

(No specific description indicates outdoor unit parts.)

The screws are loose in motor
drive element, Q200/300/400,
of outdoor control board and
rectifier, DB01/02/03.
Radiation grease was not applied
to backside of Q200, DB01,
DB02, or DB03.

Apply radiation grease as
needed Tighten screws
(Be sure to place back
the insulation sheet
between Q300/400 and
the heat sink.)

Check outdoor control board

If defective, replace it

Yes

No

Ventilation flue of heat sink
is cleared, Blower is not blocked
(Short circuit, etc.).

Remove obstacles,
Deal with short circuit

No

Yes

Check outdoor control board

If defective, replace it

No gas leakage.
Appropriate refrigerant amount.

Correct defective portion
Re-charge refrigerant

No

Yes

Pulse motor valve is normal.

Correct defective portion
Replace defective parts

No

Yes

Service valve is fully opened.

Open fully service valve

No

Yes

Piping collapse

Repair or replace pipe

Yes

No

Temperature sensor check
Discharge sensor CN603
Suction sensor CN600

Correct connector
Replace sensor

NG

OK

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 95 Monday, October 5, 2009 2:09 PM