Toshiba HWS-802XWHT6-E User Manual

Page 142

Advertising
background image

141

Toshiba

6

Compressor
Compressor lead

1. Remove defective compressor

1) Perform refrigerant gas recovery.

2) Perform the step 1-1 and step 2 and 3.

3) Remove the piping panel (Front).

Remove screws of the piping panel (Front) and
bottom board.
(Hex Ш4 Ч 10, 2 screws)
Remove screws of the piping panel (Front and
Back).
(Hex Ш4 Ч 10, 1 screw)

4) Remove the piping panel (Back).

Remove screws of the piping panel (Back) and
bottom board.
(Hex Ш4 Ч 10, 2 screws)

5) Remove the valve fixing board.

Remove the bolt of the valve.
(Hex head bolt Ш6 Ч 15, 4 bolts)
Remove the screws of the valve fixing board and
parting board.
(ST1T Ш4 Ч 8, 1 screw)
Remove the screws of the valve fixing board and
accumulator.
(ST1T Ш4 Ч 8, 1 screw)
Cut the binding tie of the discharge pipe and
suction pipe to remove each sensor and the pulse
motor valve coil lead.

6) Remove the soundproofing board. (Upper, Inward

winding, Outward winding)

7) Remove the compressor terminal cover, and then

remove the compressor lead and compressor
case thermostat.

8) Remove the TD sensor fixed to the discharge pipe.

9) Remove the compressor lead. (Leave the ferrite

core attached to the electric parts box.)
Control board U: CN200 Red

V: CN201 White
W: CN202 Black
(Torque at tightening is 1.47
±0.1N•m)

No.

Exchange parts

name

Work procedure

Remarks

Piping panel (Back)

Piping panel (Front)

TD sensor

Pipe cover

Binding tie for
heat resistance

Compressor case
thermostat

Compressor lead

TS sensor

Outlet pipe

Pipe cover, Binding tie

Pipe cover, Binding tie
Sensors (TL, TO, TE, TS)
Motorized control valve coil lead

Black pipe cover for heat resistance,
Binding tie for heat resistance
Sensors (TL, TO, TE, TD, TS)
Motorized control valve coil lead

Suction pipe

Accumulator

Compressor lead

Control board

Ferrite core

Compressor lead

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 141 Monday, October 5, 2009 2:09 PM