8-4.

Outdoor unit
control

5) Outdoor fan control
The outdoor side control part controls the number of fan motor rotations by receiving an operation instruction from the
indoor side (Hydro unit) control part.

* Although the fan motor is a DC motor, which has non-step variable numbers of rotations, it is limited to some steps for convenience of

control.

The number of fan tap rotation allocation [rpm]

5-1) Cooling fan control

• The TL sensor, TO sensor and operation frequency control the outdoor fan. The control is performed by 1 tap of

the DC fan control (14 taps).

• For 60 seconds after the start, the maximum fan tap for each zone that is shown in the following table is fixed. After

that, the fan is controlled according to the TL sensor temperature.

HWS-802H-E

HWS-1102H-E, 1402H-E

Item

Operation flow and applicable data, etc.

W1

W2

W3

W4

W5

W6

W7

W8

802H-E

200

230

260

300

340

380

420

460

1102,
1402H-E

Upper

200

240

240

260

320

380

480

500

Lower

200

200

200

280

360

400

500

520

W9

WA

WB

WC

WD

WE

WF

802H-E

520

570

600

630

670

710

740

1102,
1402H-E

Upper

530

610

640

660

720

780

890

Lower

550

630

660

700

740

820

910

TL [°C]

58

55

38

35

WE tap

+ 1 tap/20 secs
(Up to the maximum number of rotation for each zone)

- 1 tap/20 secs
(Up to the minimum number of rotation for each zone)

Number of rotation hold

Temperature range

Less than 20 Hz

20 Hz or more to less

than 45 Hz

45 Hz or more

Minimum

Maximum

Minimum

Maximum

Minimum

Maximum

38°C

TO

W6

WC

W8

WE

WA

WE

29°C TO < 38°C

W5

WB

W7

WD

W9

WD

15°C TO < 29°C

W4

W8

W6

WA

W8

WC

5°C TO < 15°C

W3

W6

W5

W8

W7

WA

0°C TO < 5°C

W2

W4

W4

W6

W5

W8

-4°C

TO < 0°C

W2

W3

W3

W5

W4

W6

TO < -4°C

OFF

OFF

OFF

W2

OFF

W3

TO abnormal

OFF

WC

OFF

WE

OFF

WE

Temperature range

Less than 20 Hz

20 Hz or more to less

than 45 Hz

45 Hz or more

Minimum

Maximum

Minimum

Maximum

Minimum

Maximum

38°C

TO

W6

WC

W8

WC

WA

WD

29°C TO < 38°C

W5

WB

W7

WC

(WB for 1102)

W9

WC

15°C TO < 29°C

W4

W8

W6

WA

W8

WC

5°C TO < 15°C

W3

W6

W5

W8

W7

WA

0°C TO < 5°C

W2

W4

W4

W6

W5

W8

-4°C

TO < 0°C

W2

W3

W3

W5

W4

W6

TO < -4°C

W1

W2

W1

W4

W2

W6

TO abnormal

W1

WC

W1

WC

W2

WD

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 59 Monday, October 5, 2009 2:09 PM