262

Language Reference • Reference

Publication 1398-PM601A-EN-P — October 2000

WORDS

Sn: TMRm

Scanned Event

Scanned Event

Purpose

A timer scanned event may be set up to start the timer based on a specified condition
and run for a time. Once the programmed time has elapsed, the specified action is exe-
cuted.

Syntax

Sn: TMRm condition action

n

The number of the scanned event. There are eight scanned events:
n = 1, 2, 3, .... , 8.

m

The number of the timer used: m = 1 or 2.

condition

The condition to be tested. The condition may be a comparison,
an input being ON or OFF, or a flag being ON or OFF.

Comparisons compare the values of two operands and determine
if the condition is TRUE or FALSE. A comparison may be
greater than (>), less than (<), equal to ( = ), not equal to (<>),
less than or equal to (< = ), or greater than or equal to (> = ). The
operands of a comparison may be user variables, system vari-
ables, analog input values (ADC), or constants.

I1 ON

;an input

F1 ON

;a user flag

INPOSN

;system flag

G1 > G2

;comparison user variable

G1 > POS1

;comparison system variable

POS2 <= 7.00

;comparison constant

action

The program statements in a scanned event routine can be any
legal program statement(s) except CALL, RETURN, JUMP,
MOVD, MOVP, DV, DIF, DELAY, DWELL, PRINT, READ,
ENABLE, and DISABLE statements. Multiple statements can be
enclosed in curly braces {}.

Remarks

The time is loaded during program execution using the TIMERn instruction. The
scanned event is enabled and disabled by Sn ON/OFF commands.

See Also

Sn: IF, Sn ON/OFF/CONT, TIMERn

Example

S2: TMR1 I11 = ON F7 = ON

S4: TMR2 POS2 < G3 V1 = V1+1