1 fault responses, Fault responses, Monitoring functions – Lenze ECSCExxx Power supply module User Manual

Page 100

Advertising
background image

Monitoring functions

Fault responses

9

l

100

EDBCSXE040 EN 7.0

9.1

Fault responses

Reaction

ð Consequence

Display

Keypad XT

RDY

IMP

Fail

TRIP / Short−circuit
braking TRIP

o

n

n

TRIP active:

ð The charging of the DC bus is stopped. With short−circuit braking
TRIP the DC bus is quickly discharged via the brake resistor.

ð The drive is coasting (no control).

ð The system bus (CAN) indicates to the master that the power
supply module is not ready for operation.

TRIP is reset:

ð The power supply module is ready for operation again.

ð The charging of the DC bus is continued.

Message

Danger!
The drive restarts automatically if the message is removed.

o

n

n

Message active:

ð The charging of the DC bus is stopped.

ð The drive is coasting (no control).

ð The system bus (CAN) indicates to the master that the power
supply module is not ready for operation.

Message is reset:

ð The power supply module is ready for operation again.

ð The charging of the DC bus is continued.

Warning

ð The failure is only displayed, the drive continues to run normally.

n

o

n

Off

STOP!
The drive can be destroyed due to deactivated monitoring
functions.

˘

˘

˘

ð There is no response to the failure.

o = off

n = on

Responses (

¶ 100) of monitoring functions can be parameterised partly via codes ˘ in the

GDC parameter menu under Monitoring.