Technical data

General data and operating conditions

3

l

21

EDBCSXE040 EN 7.0

General electrical data

EMC

Compliance with the requirements acc. to EN 61800−3

Noise emission

Compliance with the limit class C2 according to EN 61800−3(achieved with a
collective filter typical for the application)

Noise immunity

Requirements acc. to EN 61800−3

Requirement

Standard

Severity

ESD

1)

EN 61000−4−2

3, i. e.

l

8 kV for air discharge

l

6 kV for contact discharge

Conducted high frequency

EN 61000−4−6

10 V; 0.15 ... 80 MHz

RF interference (housing)

EN 61000−4−3

3, i. e. 10 V/m;
80 ... 1000 MHz

Burst

EN 61000−4−4

3/4, i. e. 2 kV/5 kHz

Surge (surge voltage on
mains cable)

EN 61000−4−5

3, i. e. 1.2/50

ms

l

1 kV phase/phase

l

2 kV phase/PE

Insulation resistance

EN 61800−5−1, UL 840: Overvoltage category III

Discharge current to PE
(Acc. to EN 61800−5−1)

> 3.5 mA AC

Enclosure

IP20 for

l

Standard installation (built−in unit)

l

Cold−plate technique

l

Mounting with thermal separation (push−through technique), IP54 on heatsink
side

Protective measures against

l

Short circuit in power terminals (short−circuit−proof at mains connection)

l

Short circuit in auxiliary circuits
– Digital outputs: Short−circuit−proof
– Bus and encoder systems: Limited protection against short circuit (if

necessary, monitoring functions can be switched off, in this case, error
messages must be reset:)

l

Earth fault (earth−fault protected at mains connection)

l

Overvoltage

Protective insulation of control circuits

Protective separation from the mains
Double/reinforced insulation acc. to EN 61800−5−1

1)

The noise immunity with the severities given must be ensured by the control cabinet. The user must check the
compliance of the severities given.