Commissioning

Setting the mains voltage

6

l

67

EDBCSXE040 EN 7.0

6.2

Setting the mains voltage

The correct mains voltage must be set in the power supply module to ensure correct
operation. The Lenze setting is the automatic adaptation of the switching thresholds for
the brake chopper operation using the mains voltage measured (C0173 = 4). Optionally,
also fixed values can be set.

ƒ

C0173 can be found in the GDC parameter menu (

^ 75) under Short setup.

(

Stop!

Inhibit the power supply module before setting the mains voltage:

ƒ

Control bit 1 (STE_RESET) = 0

ƒ

Digital input X6/DI1 = LOW

Parameterisation of the connected axis modules:

ƒ

Set the DC bus voltage thresholds of the connected axis modules via axis
module code C0173 according to the mains voltage used.

ƒ

Parameterise the charge relay function of the connected axis modules with
C0175 = 3.

ƒ

Please observe the notes given in the detailed documentation on the axis
modules!

Parameter

C0173

Designation

Mains voltage selection

Data type: INTEGER_32

Index: 24402

dec

= 5F52

hex

Mains voltage selection

^ 67
Selection list

(Lenze setting printed in bold)

Information

No response

0 Operation on 230 V mains

1 Operation on 400 V mains

2 Operation on 460 V mains

3 Operation on 480 V mains

4 Automatic determination

Switching thresholds for DC bus voltage and brake resistor

Depending on the mains voltage set in C0173, there are the following switching thresholds
for the DC−bus voltage:

Value in

C0173

Mains voltage

[V]

DC−bus voltage [V]

Brake resistor

OU error

(overvoltage threshold)

On

Off

0

230

380

370

880

1

400 ... 460

735

720

2

3

480

765

750

4

180 ... 260

380

370

261 ... 528

765

750