2 individual addressing, Individual addressing, Configuring system bus (can) – Lenze ECSCExxx Power supply module User Manual

Page 86

Advertising
background image

Configuring system bus (CAN)

Individual addressing

8

l

86

EDBCSXE040 EN 7.0

8.2

Individual addressing

C0353 can be used to determine whether the identifier (COB−ID) is created from a basic
identifier (

^^

164) plus the node address in C0350 or individually with an "ID offset" as

follows:

Identifier (COB−ID) = 384 + ID offset (C0354)

The "ID offset" can be defined via C0354.

)

Note!

The identifier for the process data input (CANx−IN) must be set the same as the
identifier of the transmitting process data output (CANx−OUT) to receive the
respective PDO telegram.

Parameter

C0353

Designation

Mode CAN_IN/OUT ID creation (COB−IDs)

Data type: INTEGER_32

Index: 24222

dec

= 5E9E

hex

C0353 can be used to determine whether the identifier (COB−ID) is created from the basic identifier plus the
node address in C0350 or individually with an ID offset in C0354.
Note:

l

This code is not active if one of the switches 2 ... 7 of the DIP switch is set to "ON".

l

After the setting, a reset node is required.

Selection list

(Lenze setting printed in bold)

Information

0 COB−ID = basic identifier + C0350

^ 164

1 COB−ID = 384 + C0354

^ 86

Subcodes

Information

C0353/1

ID creation CAN1_IN/OUT
(cyclic operation (sync−controlled))

C0353/2

ID creation CAN2_IN/OUT
(reserved)

C0353/3

ID creation CAN3_IN/OUT
(event−controlled/cyclic operation without sync)

Parameter

C0354

Designation

CAN_IN/OUT ID offset

Data type: INTEGER_32

Index: 24221

dec

= 5E9D

hex

ID offset for calculating individual COB−IDs: COB−ID = 384 + ID offset

^ 86
Note:

l

This code is not active if one of the switches 2 ... 7 of the DIP switch is set to "ON".

l

After the setting, a reset node is required.

Setting range

(min. value | unit | max. value)

0

513

Subcodes

Lenze setting

Information

C0354/1

32

ID offset for COB−ID CAN1_IN

C0354/2

160

ID offset for COB−ID CAN1_OUT

C0354/3

288

ID offset for COB−ID CAN2_IN

C0354/4

289

ID offset for COB−ID CAN2_OUT

C0354/5

416

ID offset for COB−ID CAN3_IN

C0354/6

417

ID offset for COB−ID CAN3_OUT

Advertising
This manual is related to the following products: