Appendix

General information about the system bus (CAN)

Process data transfer

12

l

153

EDBCSXE040 EN 7.0

12.3.3.2

Structure of the process data

The process data telegrams have a maximum user data length of eight bytes each.

Process data input telegram (RPDO)

ƒ

The process data input telegram transmits control information to the controller.

ƒ

The control word is transmitted in byte 1 and 2 of the user data.

Identifier

User data (8 bytes)

Control word

00

hex

00

hex

00

hex

00

hex

00

hex

00

hex

11 bits

LOW

byte

HIGH

byte

Fig. 12−4

Structure of process data input telegram (RPDO)

Process data output telegram (TPDO)

ƒ

The process data output telegram reports status information from the controller.
Status information can be as follows:
– Current status of the controller
– Status of the digital inputs
– States about internal analog values
– Fault/error messages
This information enables the higher−level host system (PLC) to respond accordingly.

ƒ

The status word 1 is transmitted in byte 1 and 2 of the user data.

ƒ

In byte 3 and 4 of the user data, the extended status word 2 can be optionally
transferred.

Identifier

User data (8 bytes)

Status word 1 Status word 2

(optional)

00

hex

00

hex

00

hex

00

hex

11 bits

LOW

byte

HIGH

byte

LOW

byte

HIGH

byte

Fig. 12−5

Structure of process data output telegram (TPDO)