8 assignment of the control word, Assignment of the control word, Configuring system bus (can) – Lenze ECSCExxx Power supply module User Manual

Page 95

Advertising
background image

Configuring system bus (CAN)

Assignment of the control word

8

l

95

EDBCSXE040 EN 7.0

8.8

Assignment of the control word

Control word to the power supply module (display in C0130)

Byte

Bit

Name

Meaning

LOW

0

STE_TOGGLE

Toggle bit: Bit state change as a "sign of life" of the
control

1

STE_RESET

0:
1:

Reset fault message
Active fault message

2

STE_KSB

0:
1:

No short−circuit braking (KSB)
Carry out short−circuit braking (KSB)

3

STE_REGLERFREIGABE

0:
1:

X6/DO1 always LOW
X6/DO1 is HIGH if the power supply module is ready for
operation and the input X6/DI2 is HIGH.

4

Free

...

7

HIGH

8

Reserved

...

10

11

Free

...

15

Advertising