4 mechanical installation, 1 important notes, Mechanical installation – Lenze ECSCExxx Power supply module User Manual

Page 25: Important notes, 4mechanical installation

Advertising
background image

Mechanical installation

Important notes

4

l

25

EDBCSXE040 EN 7.0

4

Mechanical installation

4.1

Important notes

ƒ

ECS power supply modules are provided with IP20 enclosure and can therefore only
be used for installation in control cabinets.

ƒ

If the cooling air contains air pollutants (dust, fluff, grease, aggressive gases):
– Take suitable preventive measures , e.g. separate air duct, installation of filters,

regular cleaning.

ƒ

Possible mounting positions
– Vertical at the mounting plate
– DC bus connections (X22) at the top
– Mains connection (X21) at the bottom

ƒ

Maintain the specified clearances (above and below) to other installations!
– If the ECSZS000X0B shield mounting kit is used, an additional clearance is

required.

– Ensure unimpeded ventilation of cooling air and outlet of exhaust air.
– Several modules of the ECS series can be installed in the control cabinet next to

each other without any clearance.

ƒ

The mounting plate of the control cabinet
– must be electrically conductive.
– must not be varnished.

ƒ

In case of continuous vibrations or shocks use shock absorbers.

Advertising
This manual is related to the following products: