Configuring monitoring functions

9.3.1

Mains monitoring (LP0, LP1)

Mains voltage and mains frequency (LP0)

Mains voltage and mains frequency are permanently measured. The permissible ranges
depend on the mains voltage set under C0173. The mains frequency must be within the
range from 45 to 66 Hz. If the measured values are not within these limits, an LP0 message
is activated and the DC bus cannot be charged or is disconnected from the mains.

If the power supply module is ready for operation, the limits are expanded to tolerate short
mains fluctuations. In this case, an LP0 warning is displayed.

When C0173 = 4 (automatic detection of the mains voltage), the range is defined with the
rising edge of the mains enable input.

Code

C0173

Measured values U

L1_L2

and U

L2_L3

[V]

"Not ready for operation"

"Ready for operation"

OK

LP0 message

OK

LP0 warning

LP0 message

0

207 ... 253

< 207
> 253

207 ... 253

127 ... 206
254 ... 265

< 127
> 265

1

360 ... 440

< 360
> 440

360 ... 440

280 ... 359
441 ... 460

< 280
> 460

2

414 ... 506

< 414
> 506

414 ... 506

334 ... 413
507 ... 515

< 334
> 515

3

432 ... 528

< 432
> 528

432 ... 528

352 ... 431
529 ... 540

< 352
> 540

4

Lower range

Lower range

180 ... 260

< 180
> 260

180 ... 260

100 ... 179
261 ... 265

< 100
> 265

Upper range

Upper range

261 ... 528

< 261
> 528

261 ... 528

181 ... 260
529 ... 540

< 181
> 540