Configuring system bus (CAN)

Determining the boot−up master for the drive system

8

l

88

EDBCSXE040 EN 7.0

8.3

Determining the boot−up master for the drive system

If the bus initialisation and the related state change from "Pre−Operational" to
"Operational" is not carried out by a higher−level host system (PLC), another node can be
determined as boot−up master to carry out this task.

The master functionality is only required for the initialisation phase of the drive system.
C0356 serves to set a boot up time for the master for the initialisation phase (

^

90).

By means of the NMT telegram start_remote_node (broadcast telegram) all nodes are
shifted to the NMT−state "Operational" by the master. A data exchange via the process
data objects can only be effected in this state.

The configuration is carried out via C0352.

Parameter

C0352

Designation

CAN master/slave boot−up configuration

Data type: INTEGER_32

Index: 24223

dec

= 5E9F

hex

Master/slave configuration for CAN bus interface X4

^ 88
Note: After the setting, a reset node is required.

Selection list

(Lenze setting printed in bold)

Information

0 Slave

1 Master (CAN network PDO enable)

2 Slave node guarding

Save changes with C0003 = 1.

The settings are only accepted after carrying out one of the following actions:

ƒ

Renewed switch−on of the 24 V low−voltage supply

ƒ

Reset node via the bus system (by the network management (NMT))

ƒ

Reset node with C0358 = 1

)

Note!

If reset node is executed via GDC, communication will be interrupted. You
therefore have to log in again manually or find the devices connected to the
bus once again (fieldbus scan).