Configuring system bus (can), Baud rate setting – Lenze ECSCExxx Power supply module User Manual
Page 83
Advertising
![background image](/manuals/566199/83/background.png)
Configuring system bus (CAN)
Setting the CAN node address and baud rate
Settings via DIP switch
l
83
EDBCSXE040 EN 7.0
Node address setting
The node address is set with the switches 2 ... 7 of the DIP switch. The switches are
assigned to certain valencies. The sum of the valencies make the node address to be set
(see example).
Switch
Valency
Example
Switching status
Node address
ON
OFF
ON
1
6
2
7
4
3
8
5
91
0
S1
No function
−
−
S2
32
ON
32 + 16 + 8 = 56
S3
16
ON
S4
8
ON
S5
4
OFF
S6
2
OFF
S7
1
OFF
Baud rate setting
)
Note!
The baud rate must be set identically for all CAN nodes.
Switch
Baud rate [kbit/s]
1000
500
250
125
50
ON
OFF
ON
1
6
2
7
4
3
8
5
91
0
8
ON
OFF
OFF
OFF
OFF
9
OFF
OFF
OFF
ON
ON
10
OFF
OFF
ON
OFF
ON
Advertising