Electrical installation

Power terminals

Connection to the DC bus (+U

G

, −U

G

)

5

l

45

EDBCSXE040 EN 7.0

5.3.2

Connection to the DC bus (+U

G

, −U

G

)

(

Stop!

ƒ

The supply of Lenze controllers of the 82xx and 93xx series is not permitted.

ƒ

If synchronous motors with a high centrifugal mass are used, a considerable
amount of energy can be fed back into the DC bus. Please take this into
account when dimensioning the brake resistor.

ƒ

If the total cable length is > 20 m, install an axis module or a capacitor module
directly at the power supply module.

ƒ

Design the ±U

G

cables twisted and as short as possible. Ensure short−circuit−proof

routing!

ƒ

Cable length (module

« module) > 30 cm: install shielded ±U

G

cables.

,

Documentation of the ECSxS/P/M/A axis modules

Observe the enclosed notes.

,

Documentation of the ECSxK capacitor module

Observe the enclosed notes.

Fuses

Fusing the DC−bus interconnection is not required if power supply modules of the ECS
series are used which are fused on the mains side.

Cable cross−section

Cable
length (modu
le/module)

Wire end ferrule

Cable cross−section Tightening torque

Stripping length

Up to 20 m

Without wire end
ferrule

6 mm

2

(AWG 10)

1.2 ... 1.5 Nm

(10.6 ... 13.3 lb−in)

5 mm for screw
connection

10 mm for spring
connection

With insulated wire end
ferrule

> 20 m

Without wire end
ferrule

10 mm

2

(AWG 8)

With insulated wire end
ferrule
Use pin−end connectors
for wiring!