Electrical installation

Power terminals

Mains connection

5

l

43

EDBCSXE040 EN 7.0

5.3.1

Mains connection

Important notes

ƒ

Keep the cables between the RFI filter and the power supply module as short as
possible.
– Make sure that no short−circuit can occur!

ƒ

Mains cables and ±U

G

cables must not contact each other.

ƒ

When mains cables and ±U

G

cables are laid in parallel:

– Cable distance: > 150 mm

ƒ

Cable length > 30 cm:
– Shield the cables between the RFI filter and the power supply module to comply

with the general EMC Directive.

ƒ

With some 24 V switched−mode power supplies, the EMC limit values for the system
will only be met if the power supplies are connected to ECSZZ series RFI filters.
Please contact the manufacturer of the power supply unit on the compliance with
EMC limit values for conducted interference.

,

Documentation of the RFI filter ECSZZ...

Observe the enclosed notes.

Wiring variants for the ECSxE power supply module



‚