Mechanical installation

Mounting in cold−plate design

4

l

32

EDBCSXE040 EN 7.0

4.4

Mounting in cold−plate design

The ECSCE series power supply modules are intended for mounting in cold plate technique
(e.g. on collective coolers).

Requirements for collective coolers

The following requirements must be met to ensure safe and reliable operation of the
power supply modules:

ƒ

Good thermal contact with the cooler:
– The contact surface between collective cooler and power supply module must be

at least as large as the cooling plate of the power supply module.

– Smooth contact surface, max. deviation 0.05 mm.
– Use all prescribed screwed connections to connect the collective cooler to the

power supply module.

ƒ

Comply with the thermal resistance R

th

according to the table.

– The values are valid for operation of the power supply modules under rated

conditions.

Power supply
module

Power to be dissipated

Heatsink ˘ environment

Type

Ploss [W]

R

th

[k/W]

ECSCE012

30.0

0.45

ECSCE020

45.0

0.34

ECSCE040

81.0

0.17

ƒ

Ambient conditions:
– The rated data regarding the ambient temperature remain valid for the power

supply modules (

^ 20 ff.).

– Temperature of the cooling plate ("cold plate"): max. +85 °C