Monitoring functions – Lenze ECSCExxx Power supply module User Manual

Page 104

Advertising
background image

Monitoring functions

Configuring monitoring functions
Mains monitoring (LP0, LP1)

9

l

104

EDBCSXE040 EN 7.0

Permissible ranges from ECSxE operating system V5.0:

Code

C0173

Measured values U

L1_L2

and U

L2_L3

[V]

"Not ready for operation"

"Ready for operation"

OK

LP0 message

OK

LP0 warning

LP0 message

0

195.5 ... 264.5

(+/− 15 %)

< 195.5
> 264.5

195.5 ... 264.5

(+/− 15 %)

172.5 ... 195.5

(− 25 %)

264.5 ... 276

(+ 20 %)

< 172.5

> 276

1

340 ... 460

(+/− 15 %)

< 340
> 460

340 ... 460

(+/− 15 %)

300 ... 340

(− 25 %)

460 ... 480

(+ 20 %)

< 300
> 480

2

391 ... 506

(+/− 15 %)

< 391
> 506

391 ... 506

(+/− 15 %)

345 ... 391

(− 25 %)

506 ... 517.5

(+ 12.5 %)

< 345

> 517.5

3

408 ... 528

(+/− 15 %)

< 408
> 528

408 ... 528

(+/− 15 %)

360 ... 408

(− 25 %)

528 ... 540

(+ 12.5 %)

< 360
> 540

4

Lower range

Lower range

180 ... 260

< 180
> 260

180 ... 260

100 ... 179
261 ... 265

< 100
> 265

Upper range

Upper range

261 ... 528

< 261
> 528

261 ... 528

181 ... 260
529 ... 540

< 181
> 540

Mains phase failure (LP1)

From the operating system V2.1 onwards, the power supply module monitors the mains
for phase failure. A phase failure will be detected after half a mains period because the
mains synchronisation is faulty. If the DC bus is charged and the power supply module is
ready for operation, an LP1 warning is triggered. For all other states an LP1 message is
triggered to prevent a charging process with faulty synchronisation. The LP1
warning/message will be deactivated when the mains synchronisation has been free of
faults for 2 mains periods.

Under C0599 a time interval for triggering an LP1 TRIP can be set in addition. If an LP1
warning or an LP1 message is active for the time interval set under C0599, an LP1−TRIP is
triggered. C0599 = 65535 ms deactivates the LP−TRIP. In this case, only an LP1 warning or
an LP1 message is triggered.

Parameter

C0599

Designation

Delay time − system disturbance (LP1)

Data type: INTEGER_32

Index: 23976

dec

= 5DA8

hex

If an LP1 warning or LP1 message is active for the set time, an LP1−TRIP is enabled.

l

Value < 65535 ms: LP1−TRIP

l

Value = 65535 ms: LP1 warning/LP1 message

^ 103
Setting range

(min. value | unit | max. value)

Lenze setting

0

ms

65535 65535 ms