Diagnostics – Lenze ECSCExxx Power supply module User Manual

Page 114

Advertising
background image

Diagnostics

Advanced diagnostics via diagnostics PDO (CAN2_OUT)

10

l

114

EDBCSXE040 EN 7.0

Size

Description

Value

C0390/1 ... 8

8

Internal error bits:

l

Bit 0 = 1: An Ixt overload has occurred.

l

Bit 1 = 1: The internal brake resistor is overloaded.

l

Bit 2 = 1: The external temperature contact is open.

l

Bit 3 = 1: A short circuit of the brake IGBT has occurred.

l

Bit 4 = 1: An LP0 error has occurred.

l

Bit 5 = 1: An LP1 error has occurred.

l

Bit 6 = 1: No short−circuit braking possible.

l

Bit 7 = 1: A U15 error has occurred (2 monitoring cycles below 17 V).

l

Bit 8 = 1: The 24V supply was lower than the 17V monitoring threshold.

l

Bit 9 ... 15: Not assigned.

2 bytes

Advertising
This manual is related to the following products: