2 settings via codes, Settings via codes, Configuring system bus (can) – Lenze ECSCExxx Power supply module User Manual

Page 84

Advertising
background image

Configuring system bus (CAN)

Setting the CAN node address and baud rate
Settings via codes

8

l

84

EDBCSXE040 EN 7.0

8.1.2

Settings via codes

)

Note!

ƒ

The settings in C0350 (CAN node address) and C0351 (baud rate) are only
used if the (address) switches 2 ... 7 of the DIP switch S1 are switched off
(OFF).

ƒ

If only one (address) switch 2 ... 7 is switched on (ON), the settings of the DIP
switch S1 usually apply.

ƒ

The baud rate (C0351) must be set identically for all CAN bus nodes.

ƒ

If the Lenze setting has been loaded via C0002,
– C0351 is set to 0 (500 kbit/s);
– you have to reset the baud rate (C0351) and the CAN node address

(C0350).

Parameter

C0350

Designation

CAN node address

Data type: INTEGER_32

Index: 24225

dec

= 5EA1

hex

Setting of the CAN node address
Note:

l

This code is not active if one of the switches 2 ... 7 of the DIP switch is set to "ON". (

^ 82)

l

After the setting, a reset node is required.

l

Each CAN node must be assigned a definite node address.

Setting range

(min. value | unit | max. value)

Lenze setting

1

63 32

Parameter

C0351

Designation

CAN baud rate

Data type: INTEGER_32

Index: 24224

dec

= 5EA0

hex

Entry of the CAN baud rate
Note:

l

The baud rate must be set identically for all CAN nodes.

l

This code is not active if one of the switches 2 ... 7 of the DIP switch is set to "ON". (

^ 82)

l

After the setting, a reset node is required.

Selection list

(Lenze setting printed in bold)

Information

0 500 kbps

1 250 kbps

2 125 kbps

3 50 kbps

4 1000 kbps