Appendix, Codes – Lenze ECSCExxx Power supply module User Manual

Page 136

Advertising
background image

Appendix

Codes

12

l

136

EDBCSXE040 EN 7.0

Parameter

C0350

Designation

CAN node address

Data type: INTEGER_32

Index: 24225

dec

= 5EA1

hex

Setting of the CAN node address
Note:

l

This code is not active if one of the switches 2 ... 7 of the DIP switch is set to "ON". (

^ 82)

l

After the setting, a reset node is required.

l

Each CAN node must be assigned a definite node address.

Setting range

(min. value | unit | max. value)

Lenze setting

1

63 32

Parameter

C0351

Designation

CAN baud rate

Data type: INTEGER_32

Index: 24224

dec

= 5EA0

hex

Entry of the CAN baud rate
Note:

l

The baud rate must be set identically for all CAN nodes.

l

This code is not active if one of the switches 2 ... 7 of the DIP switch is set to "ON". (

^ 82)

l

After the setting, a reset node is required.

Selection list

(Lenze setting printed in bold)

Information

0 500 kbps

1 250 kbps

2 125 kbps

3 50 kbps

4 1000 kbps

Parameter

C0352

Designation

CAN master/slave boot−up configuration

Data type: INTEGER_32

Index: 24223

dec

= 5E9F

hex

Master/slave configuration for CAN bus interface X4

^ 88
Note: After the setting, a reset node is required.

Selection list

(Lenze setting printed in bold)

Information

0 Slave

1 Master (CAN network PDO enable)

2 Slave node guarding

Parameter

C0353

Designation

Mode CAN_IN/OUT ID creation (COB−IDs)

Data type: INTEGER_32

Index: 24222

dec

= 5E9E

hex

C0353 can be used to determine whether the identifier (COB−ID) is created from the basic identifier plus the
node address in C0350 or individually with an ID offset in C0354.
Note:

l

This code is not active if one of the switches 2 ... 7 of the DIP switch is set to "ON".

l

After the setting, a reset node is required.

Selection list

(Lenze setting printed in bold)

Information

0 COB−ID = basic identifier + C0350

^ 164

1 COB−ID = 384 + C0354

^ 86

Subcodes

Information

C0353/1

ID creation CAN1_IN/OUT
(cyclic operation (sync−controlled))

C0353/2

ID creation CAN2_IN/OUT
(reserved)

C0353/3

ID creation CAN3_IN/OUT
(event−controlled/cyclic operation without sync)

Advertising