10 diagnostics, 1 diagnostics with global drive control (gdc), Diagnostics – Lenze ECSCExxx Power supply module User Manual

Page 110: Diagnostics with global drive control (gdc)

Advertising
background image

Diagnostics

Diagnostics with Global Drive Control (GDC)

10

l

110

EDBCSXE040 EN 7.0

10

Diagnostics

10.1

Diagnostics with Global Drive Control (GDC)

Different system values and fault messages can be read in the GDC parameter menu under
Diagnostics via the following codes:

Parameter

C0050

Designation

Mains voltage (V

rms

) between phases L1−L2

Data type: INTEGER_32

Index: 24525

dec

= 5FCD

hex

Display of the mains voltage (V

rms

) between phases L1 and L2

Display range

(min. value | unit | max. value)

−16383

V

16383

Parameter

C0051

Designation

Mains voltage (V

rms

) between phases L2−L3

Data type: INTEGER_32

Index: 24524

dec

= 5FCC

hex

Display of the mains voltage (V

rms

) between phases L2 and L3

Display range

(min. value | unit | max. value)

−16383

V

16383

Parameter

C0053

Designation

DC−bus voltage (U

G

)

Data type: INTEGER_32

Index: 24522

dec

= 5FCA

hex

Display of the DC−bus voltage (U

G

)

Display range

(min. value | unit | max. value)

−32767

V

32767

Parameter

C0054

Designation

Mains current (r.m.s. value)

Data type: INTEGER_32

Index: 24521

dec

= 5FC9

hex

Display of the mains current (r.m.s. value)

Display range

(min. value | unit | max. value)

−1638.3

A

1638.3

Parameter

C0055

Designation

Voltage across the brake resistor

Data type: INTEGER_32

Index: 24520

dec

= 5FC8

hex

Display of the voltage across the brake resistor

Display range

(min. value | unit | max. value)

−32767

V

32767

Parameter

C0057

Designation

Mains frequency

Data type: INTEGER_32

Index: 24518

dec

= 5FC6

hex

Display of the mains frequency

Display range

(min. value | unit | max. value)

−3276.7

Hz

3276.7

Advertising