Appendix

Codes

12

l

126

EDBCSXE040 EN 7.0

12

Appendix

12.1

Codes

Parameter

C0001

Designation

Operating mode

Data type: INTEGER_32

Index: 24574

dec

= 5FFE

hex

Selection of the operating mode (control)

Selection list

(Lenze setting printed in bold)

Information

0 System bus (CAN) control word

^ 64

1 Control via dig. inputs

^ 65

2 Control word via automation

interface (AIF)

^ 66

Parameter

C0002

Designation

Load Lenze setting

Data type: INTEGER_32

Index: 24573

dec

= 5FFD

hex

Note: The Lenze setting can only be loaded if the controller is inhibited.

Selection list

(Lenze setting printed in bold)

Information

0 Load Lenze setting

1 Loading executed

Parameter

C0003

Designation

Save parameter set

Data type: UNSIGNED_32

Index: 24572

dec

= 5FFC

hex

Setting for saving the parameter set

Selection list

(Lenze setting printed in bold)

Information

0 No response

1 Save parameter set

Parameter

C0004

Designation

Selection of XT keypad status display

Data type: INTEGER_32

Index: 24571

dec

= 5FFB

hex

The XT keypad displays the selected code in the operating level if no other status messages from C0183 are
active.

l

Example: 53 = C0053 (DC−bus voltage)

Setting range

(min. value | unit | max. value)

Lenze setting

0

989 53

Parameter

C0009

Designation

LECOM device address

Data type: INTEGER_32

Index: 24566

dec

= 5FF6

hex

Entry of the device address for operation via AIF interface
Communication modules on AIF interface:

l

LECOM−A/B/LI 2102

l

PROFIBUS−DP 2133

Setting range

(min. value | unit | max. value)

Lenze setting

0

99 1