Electrical installation

Power terminals

5

l

42

EDBCSXE040 EN 7.0

Cable cross−sections and screw−tightening torques

Cable type

Wire end ferrule

Possible cable
cross−sections

Tightening torque

Stripping length

Terminal strips X21 and X22

Rigid

˘

0.2 ... 10 mm

2

(AWG 24 ... 8)

1.2 ... 1.5 Nm

(10.6 ... 13.3 lb−in)

5 mm for screw
connection

10 mm for spring
connection

Flexible

Without wire end
ferrule

0.2 ... 10 mm

2

(AWG 24 ... 8)

With insulated wire
end ferrule

0.25 ... 6 mm

2

(AWG 22 ... 10)

With insulated TWIN
wire end ferrule

0.25 ... 4 mm

2

(AWG 22 ... 12)

Shielded cables

The following factors decisively determine the effect of the shielded cables:

ƒ

Good shield connection
– Ensure a contact surface as large as possible

ƒ

Low shield resistance
– Only use shields with tin−plated or nickel−plated copper braids (shields with steel

braids cannot be used).

ƒ

High overlap rate of the braid
– At least 70 ... 80 % with 90° overlap angle

The ECSZS000X0B shield mounting kit includes a wire clamp and shield sheet.