Electrical installation

Power terminals
Connection plan for mimimum wiring with internal brake resistor

5

l

46

EDBCSXE040 EN 7.0

5.3.3

Connection plan for mimimum wiring with internal brake resistor

(

Stop!

Always operate the ECS power supply modules with a brake resistor
(internal/external).

The ECS power supply modules in the standard built−in unit and push−through design
(ECSEE / ECSDE) are provided with a device−internal brake resistor.

In order to use the internal brake resistor (Rb), carry out the following wiring:

ƒ

Bridge between the terminals X22/+UG and X22/BR0 (CR)
Current flow from +UG via the internal brake resistor (Rb) and the brake transistor to
−UG.

ƒ

Bridge between the terminals X6/T1 and X6/T2 (CR)
Deactivate the temperature monitoring of the non−existing external brake resistor.

L3

N

L1

L2

Z1

K1

K1

L1

L2

L3

PE

X21

+UG

+UG +UG

-UG

-UG

-UG

PE

PE

PE

X22

X23

Off

On

+UG

BR1

BR0

M

3~

R

T1

T2

X6

...

J

2

6

K1

0

Rb

U

V

W PE

X24

BD1 BD2

X25

X7

"

"

+

"

"

+UG +UG

-UG

-UG

PE

PE

X23

M

3~

R

J

2

6

0

U

V

W PE

X24

BD1 BD2

X25

X7

+

"

"

"

"

F4

F1...F3

"
"

ECSxS/P/M/A...

ECSEE...

ECSDE...

ECSxS/P/M/A...

ECSXA011

Fig. 5−3

Interconnected power system with internal brake resistor

"

HF−shield termination by large surface connection to functional earth (see mounting
instructions for shield mounting ECSZS000X0B)
Twisted cables

K1

Mains contactor

F1 ... F4 Fuse
Z1

Mains choke / mains filter, optional

Rb

Internal brake resistor

J

KTY thermal sensor of the motor

0

System cable for feedback