2 table of attributes, Appendix, Table of attributes – Lenze ECSCExxx Power supply module User Manual

Page 144

Advertising
background image

Appendix

Table of attributes

12

l

144

EDBCSXE040 EN 7.0

12.2

Table of attributes

The table of attributes contains information required for communicating with the ECSxE
power supply module via parameters.

How to read the table of attributes:

Column

Meaning

Entry

Code

Name of the Lenze code

Cxxxx

Name

Parameter short text

Text

Index

dec

Index under which the parameter is addressed.
The subindex for array variables corresponds to
the Lenze subcode number.

24575 − Lenze code number

Only required for control via bus
system.

hex

5FFFh − Lenze code number

Data

DS

Data structure

E

Single variable
(only one parameter element)

A

Array variable
(several parameter elements)

DA

Number of array elements (subcodes)

Quantity

Data type Indication of the data type

BITFIELD_8

1 byte bit coded

BITFIELD_16

2 byte bit coded

BITFIELD_32

4 byte bit coded

INTEGER_8

1 byte with sign

INTEGER_16

2 bytes with sign

INTEGER_32

4 bytes with sign

UNSIGNED_8

1 byte without sign

UNSIGNED_16

2 bytes without sign

UNSIGNED_32

4 bytes without sign

VISIBLE_STRING

ASCII string

Factor

Factor for data transmission via bus system,
depending on the number of decimal positions

1, 10, 100, or 1000

1

º no decimal position

10

º 1 decimal position

100

º 2 decimal positions

1000

º 3 decimal positions

Access

R

Read access

ü Reading allowed

W

Write access

ü Writing allowed

CINH

Controller inhibit required

ü Writing only possible when controller is inhibited

Table of attributes

Code

Designation

Index

Data

Access

dec

hex

DS

DA

Data type

Factor

R

W

CINH

C0001

Operating mode

24574

5FFE

E

1

INTEGER_32

10000

ь

ь

C0002

Load Lenze setting

24573

5FFD

E

1

INTEGER_32

10000

ь

ь

ь

C0003

Save parameter set

24572

5FFC

E

1

INTEGER_32

10000

ь

ь

C0004

Selection of XT keypad status display

24571

5FFB

E

1

INTEGER_32

10000

ь

ь

C0009

LECOM device address

24566

5FF6

E

1

INTEGER_32

10000

ь

ь

C0022

Max. charging current after power
supply enable

24553

5FE9

E

1

INTEGER_32

10000

ь

ь

C0023

Peak current (peak)

24552

5FE8

E

1

INTEGER_32

10000

ü

C0024

Service code

24551

5FE7

E

1

INTEGER_32

10000

ь

ь

C0028

Service code

24547

5FE3

E

1

INTEGER_32

10000

ь

ь

C0029

Service code

24546

5FE2

E

1

INTEGER_32

10000

ь

ь

C0031

Service code

24544

5FE0

E

1

INTEGER_32

10000

ь

ь

C0040

Power supply enable − power supply
module

24535

5FD7

E

1

INTEGER_32

10000

ь

ь

C0043

Reset fault message

24532

5FD4

E

1

INTEGER_32

10000

ь

ь

C0050

Mains voltage (V

rms

) between phases

L1−L2

24525

5FCD

E

1

INTEGER_32

10000

ü

C0051

Mains voltage (V

rms

) between phases

L2−L3

24524

5FCC

E

1

INTEGER_32

10000

ü

C0053

DC−bus voltage (U

G

)

24522

5FCA

E

1

INTEGER_32

10000

ь

Advertising